LLH300P Hydraulic Separator

Home PageLLH300P Hydraulic Separator

Rhella LLH300P hydraulic separator with dirt magnet

Hydraulic separator

LLH300P

Hydraulic separator with dirt magnet

The Rhella LLH300P combines four functions in one 304 stainless steel vessel: it separates the primary (boiler or chiller) circuit from the secondary (system) circuits so each pump runs without disturbing the other, and it removes air, dirt and ferrous particles from the water. Sized for 110 gpm at 4 ft/s, with 3″ ASME B16.5 Class 150 flange connections.

110 gpmFlow at 4 ft/s 3″Connections 150 psiMax. pressure 210 °FMax. temperature

4-in-1 performance

1

Hydraulic separation

A low-velocity zone between the primary and secondary connections decouples the boiler and system pumps.

2

Air removal

The stainless Pall ring media merges micro-bubbles so they rise to the automatic air vent.

3

Dirt removal

Slow water lets dirt settle to the bottom, where it is flushed out through the drain.

4

Magnetite removal

A 12,000 gauss neodymium rod in a dry well holds ferrous particles; pull the rod to release them.

Dimensions

LLH300P dimensional drawing

Dimensions, mm / in

ABCDEF
mm473806178350278273
in18.631.77.013.810.910.7

A Width across the connection faces · B Overall height of the vessel · C Top of vessel to upper connections · D Between upper and lower connections · E Lower connections to bottom of vessel · F Vessel outside diameter. Heights exclude the air vent, drain valve and fittings.

Connections

#PortSize and type
1Primary and secondary connections (4)3″ ASME B16.5 Class 150 flange
2Air vent port½″ GM
3Drain¾″ FNPT
4Dirt magnet portdry well with removable rod
5Gauge port¼″ FNPT
6Temperature sensor wells (2)Ø8 × 40 mm, one in the primary supply and one in the secondary supply connection
7Fill / makeup water port, on the side (expansion tank or system fill)¾″ FNPT

Technical data

Flow at 4 ft/s110 gpm (24.9 m³/h)
Pressure drop at 4 ft/s0.53 ft primary / 0.53 ft secondary
Max. operating pressure150 psi (10 bar)
Operating temperature32–210 °F (0–99 °C)
FluidsWater, or water with up to 50 % glycol
VesselØ 273 × 3 mm, 304 stainless steel
Coalescing elementTwo stainless steel wire cages filled with Ø25 mm 304 stainless steel Pall rings (4.8 kg)
Dirt magnetØ25 mm neodymium rod, M50 grade, 12,000 gauss, in a dry well
Weight88 lb (39.9 kg), shipping 135 lb
Water volumeapprox. 10.9 US gal
Warranty2 years

Performance

Pressure drop

LLH300P pressure drop chart

Primary side: supply to return connection. Secondary side: return to supply connection. Computed with 3D CFD of the vessel and its internals; pressure drop rises with the square of the flow.

Separation performance

LLH300P separation performance chart

Unwanted mixing: share of the heat that should reach the system but returns to the boiler instead. 3D CFD with buoyancy, 20 °F design ΔT, primary at 110 gpm. Mixing at balanced flow 22.1 %; onset (≥ 5 %): 62–236 gpm; breakdown (≥ 15 %): 88–141 gpm.

How to read the separation chart (click to open)

A hydraulic separator joins two loops: the primary loop, with the boiler (or chiller) and its pump, and the secondary loop, with the heating system and its pumps. Hot water from the boiler should go out to the system, and the cooler water coming back from the system should go back to the boiler. Some of the hot water can instead turn around inside the separator and go straight back to the boiler. This is called unwanted mixing, and the chart shows how much of it happens.

  • Across the bottom is how much water the system pumps draw, in gpm. The boiler pump stays at 110 gpm, the LLH300P’s rated flow.
  • Up the side is unwanted mixing: the share of the boiler’s heat that returns to the boiler instead of reaching the system. 0 % is perfect; 10 % means 10 of every 100 units of heat come straight back.
  • The dotted line marks the point where the system draws exactly as much water as the boiler pump delivers. Mixing is usually highest near this line and falls off on either side.

The coloured zones

  • White, below 5 %: the separator works as intended. The effect is too small to notice.
  • Yellow, 5 to 15 %: some hot water short-circuits back to the boiler. The boiler gets slightly warmer return water and the system slightly cooler supply water. A condensing boiler loses a little efficiency.
  • Red, above 15 %: separation is breaking down. A large share of the heat circulates back to the boiler: a condensing boiler condenses less and runs less efficiently, the boiler may switch on and off more often, and the system may not reach the supply temperature it was designed for.

What this means for the LLH300P: The curve enters the red zone when the system draws 88 to 141 gpm, and peaks at 22.1 % when the system and the boiler pump move the same 110 gpm. At that point about 22 of every 100 units of the boiler’s heat go straight back to the boiler instead of out to the system. Mixing stays below 5 % only when the system draws less than 62 gpm or more than 236 gpm.

The curve comes from 3D computer flow simulations (CFD) at a 20 °F temperature difference between supply and return. A real installation can differ somewhat with piping layout and temperatures.

Sizing and installation

Select the separator for the larger of the primary and secondary flows. The listed flow is the flow at 4 ft/s in the connections, a reference point and not a limit; higher flows are possible with higher pressure drop.

Install vertically with the vent at the top, the primary circuit on one side and the secondary on the other: supply connections at the upper pair, returns at the lower pair. Keep straight pipe of at least 5 pipe diameters before each inlet, and provide isolation valves so the magnet and drain can be serviced.

Maintenance

Open the drain periodically to blow down settled dirt. To release the collected magnetite, pull the rod out of its dry well: the magnetite drops to the bottom and is flushed out at the next blowdown. The automatic air vent needs no routine service.

Typical specification

Furnish and install a Rhella LLH300P hydraulic separator, or approved equal, selected for 110 gpm (4 ft/s connection velocity). The separator shall combine hydraulic separation of the primary and secondary circuits with air, dirt and ferrous-particle removal in one vessel. The vessel shall be 304 stainless steel with 3″ ASME B16.5 Class 150 flange primary and secondary connections, internal two stainless steel wire cages filled with Ø25 mm 304 stainless steel Pall rings (4.8 kg), an automatic air vent at the top, a drain at the bottom, a fill port, and a removable 12,000 gauss neodymium rod magnet in an external dry well. Maximum working pressure 150 psi; working temperature 32–210 °F; suitable for water and glycol solutions up to 50 %.